AASHTO/AWS D1.5:2025 · Tabla 12.4/12.5 · Fractura Crítica · H8

Precalentamiento M270M Gr.250 — H8, Low HI, ≤ 20 mm: 125°F

Requisito de precalentamiento de fractura crítica para M270M Gr.250 / M270 Gr.36 en espesor ≤ 20 mm (3/4 in) con designación de hidrógeno H8, según AASHTO/AWS D1.5:2025, el Código de Soldadura de Puentes.

Basado en AWS D1.5:2025 — cada valor trazado a la cláusula.

Precalentamiento e Interpaso Mínimo de Fractura Crítica
125°F / 50°C
Hidrógeno H8 · aporte térmico 1.2–2.0 kJ/mm · espesor ≤ 20 mm (3/4 in)
AASHTO/AWS D1.5M/D1.5:2025 Tabla 12.4/12.5
Designación H8: el consumible deposita ≤ 8 mL/100g de hidrógeno difusible según AWS A4.3. Menor hidrógeno = menor precalentamiento.
Herramienta de referencia. Verificar contra la edición aplicable al proyecto y WPS aprobada por el Ingeniero.

M270M Gr.250 / M270 Gr.36

AASHTO M270M Gr.250 (M270 Gr.36) is the metric/US customary designation for the basic structural bridge steel with 250 MPa (36 ksi) minimum yield. It is the direct bridge equivalent of ASTM A709 Gr.36, procured under AASHTO M270 with mandatory Charpy V-notch testing per temperature zone. Used for secondary bridge members — lateral bracing, diaphragm plates, floor beam stiffeners, and bearing components where Gr.345 strength is not needed. Non-fracture-critical preheat follows Table 6.3 Group 1; fracture-critical follows Tables 12.4/12.5 with hydrogen and heat input as additional variables.

Entendiendo el Precalentamiento FC para M270M Gr.250 / M270 Gr.36

Basic 250 MPa (36 ksi) bridge steel for secondary members. Under D1.5 fracture-critical requirements (Clause 12), the combination of H8 hydrogen designation and this heat input band requires 125°F minimum preheat at ≤ 20 mm (3/4 in). Lower hydrogen levels (H4 < H8 < H16) allow lower preheat because less hydrogen enters the weld deposit. Similarly, higher heat input reduces preheat requirements because slower cooling rates give hydrogen more time to diffuse out.

Dónde se Usa M270M Gr.250 / M270 Gr.36

Specified for secondary bridge members under AASHTO LRFD — lateral bracing angles, diaphragm plates, floor beam stiffeners, bearing seat components, and railing posts. Gr.250 (36) requires CVN testing per AASHTO temperature zone, distinguishing it from plain ASTM A36 by guaranteeing fracture resistance at the bridge design service temperature. Transverse stiffener fillet welds and floor beam web-to-flange joints are high-frequency fabrication details. Temperature zones (1 through 3) determine CVN test temperature: Zone 1 at 21°C (70°F) for moderate climates, Zone 2 at 4°C (40°F) for cold, Zone 3 at -12°C (10°F) for severe cold.

Control de Hidrógeno H8 para M270M Gr.250 / M270 Gr.36

H8 designation (8 mL/100g max) on Gr.250 (36) provides a balanced approach between preheat economy and consumable availability. Most structural SMAW electrodes and FCAW wires carry H8 classification as the standard low-hydrogen tier. For secondary bridge members, H8 is typically the default specification unless the Engineer specifically mandates H4.

Por qué el Precalentamiento Importa en ≤ 20 mm (3/4 in)

Material up to 20 mm (3/4 in) covers most cross-frame angles, stiffener clips, lateral bracing members, and light bridge plate. At this thickness, hydrogen diffusion is efficient and preheat requirements are the lowest in Table 6.3 — 10°C (50°F) for both groups. In FC service, this thickness tier also carries the lowest preheat in Tables 12.4–12.7, starting at 40°C (100°F) for H4 consumables.

M270M Gr.250 / M270 Gr.36 en ≤ 20 mm (3/4 in)

Gr.250 (36) at up to 20 mm is the lightest bridge fabrication scenario — cross-frame angles, stiffener clips, and lateral bracing gussets. Hydrogen diffusion through this thin section is rapid, so preheat has the least influence on cracking resistance. Most fabricators use E7018 SMAW for short fillet welds at this thickness because the joint lengths are too short for mechanized FCAW setup to be economical. Interpass monitoring is minimal at this tier because heat builds slowly in thin plate.

Otros Aceros de Puente en H8 1.2–2.0 kJ/mm · ≤ 20 mm (3/4 in)

AceroTablaPrecalentamiento
M270M Gr.345W / M270 Gr.50WB125°F (50°C)
M270M HPS345W / M270 HPS50WB125°F (50°C)
M270M HPS485W / M270 HPS70WB125°F (50°C)
M270M Gr.345 / M270 Gr.50A125°F (50°C)

Prueba Diferentes Combinaciones

Usa la Calculadora de Precalentamiento D1.5 para Puentes para consultar cualquier acero AASHTO M270, nivel de hidrógeno y combinación de aporte térmico. También consulta la Calculadora de Precalentamiento D1.1 para acero estructural.

¿Cuál es el precalentamiento FC para M270M Gr.250 / M270 Gr.36 con H8 en ≤ 20 mm (3/4 in)?
Para fractura crítica M270M Gr.250 / M270 Gr.36 soldado con consumibles designados H8 en espesor ≤ 20 mm (3/4 in) y aporte térmico 1.2–2.0 kJ/mm, el precalentamiento mínimo es 125°F (50°C) según D1.5 Tabla 12.4/12.5.
¿Cuál es la diferencia entre precalentamiento FC y NFC para M270M Gr.250 / M270 Gr.36?
El precalentamiento no fractura crítica (Tabla 6.3) es una consulta simple basada en espesor. El de fractura crítica (Tablas 12.4–12.8) agrega nivel de hidrógeno y aporte térmico como variables, típicamente requiriendo mayor precalentamiento.
¿Cómo afecta el aporte térmico al precalentamiento FC de M270M Gr.250 / M270 Gr.36?
Mayor aporte térmico significa velocidades de enfriamiento más lentas, dando más tiempo al hidrógeno para difundirse fuera de la zona de soldadura. En 1.2–2.0 kJ/mm, el precalentamiento de 125°F equilibra el nivel de hidrógeno y la velocidad de enfriamiento.
Is preheat needed for bridge steel under 20 mm?
Yes — D1.5 Table 6.3 requires a minimum of 10°C (50°F) even for the thinnest material in both groups. This is higher than D1.1’s Category B minimum of 0°C (32°F) at the same thickness, reflecting the more conservative approach for bridge structures where fracture consequences are severe.