CWI Exam · Part C · Code Application

CWI Practice Questions — D1.1 Code Application

CWI Part C 시험은 시간 압박 속에서 용접 코드 탐색 및 적용 능력을 평가합니다. 이 연습 문제는 D1.1:2025 코드 적용 — 예열 조회, 필릿 용접 크기 결정, 사전 인증 규칙 및 필수 변수에 중점을 둡니다. 각 답변은 특정 조항 또는 표 참조를 인용합니다.

이 질문들을 사용하는 방법: 시나리오를 읽고, 답변을 시도한 다음, 해답을 확인하십시오. 각 답변은 특정 D1.1 조항 또는 표를 인용합니다. 위에 있는 Flux를 사용하여 어려운 주제에 대한 추가 질문을 하십시오.

예열 — 표 5.11

Q1: A572 Gr.50 plate, 1 inch thick, welded with FCAW using E71T-1. What is the 최소 예열?
Answer: 50°F (10°C). A572 Gr.50 is Group II in Table 5.11. E71T-1 is a 저수소 전극, placing it in 범주 B. For Group II, Category B, 두께 over 3/4 through 1-1/2 inch: minimum preheat is 50°F.
Q2: Same steel and thickness, but the welder switches to E71T-11 (self-shielded FCAW). Does the preheat change?
Answer: Yes — dramatically. E71T-11 is a 비저수소 electrode, moving the WPS to Category A in Table 5.11. For Group II, Category A, 1 inch thickness: minimum preheat jumps to 150°F (65°C). This is a common exam trap — the only change is the electrode classification, but the preheat triples.

필릿 용접 크기 — Table 7.7

Q3: You are 용접 a 1/2-inch plate to a 3/4-inch plate using E7018 (SMAW). What is the minimum 필릿 용접 크기 per Table 7.7?
Answer: 3/16 inch. Per Table 7.7 Footnote A, when using a low-hydrogen process (E7018), T equals the thinner part joined (1/2 inch). For T over 1/4 through 1/2 inch, minimum fillet 크기 is 3/16 inch. If the welder used a non-low-hydrogen process without preheat, T would equal the thicker part (3/4 inch), requiring 1/4 inch minimum.
Q4: The Engineer specifies a 3/16-inch 필릿 용접 on 1-1/4-inch thick A36 plate using E6013 without preheat. Is this acceptable?
Answer: No. E6013 is a non-low-hydrogen electrode, so per Table 7.7 Footnote A, T equals the thicker part (1-1/4 inch). For T over 3/4 inch, minimum fillet size is 5/16 inch. The 3/16-inch 용접 is undersized. Additionally, Table 5.11 requires 150°F preheat for Group I, Category A at this thickness (over 3/4 thru 1-1/2 inch) — but the scenario says no preheat was applied, which is also non-compliant.

사전 인증 WPS — 조항 5

Q5: A fabricator wants to prequalify a WPS using GMAW short-circuit transfer on 1/2-inch A36 plate. Can this be prequalified?
Answer: No. D1.1:2025 Clause 5 does not include GMAW with short-circuiting transfer (GMAW-S) from prequalification. The fabricator must qualify the procedure by 시험 under Clause 6. Spray transfer, globular transfer, and pulsed-spray GMAW are prequalified when all other Clause 5 conditions are met.
Q6: Can a prequalified WPS use a single-V groove joint with a root opening less than the D1.1 minimum?
Answer: No. Prequalified joint dimensions must conform to the tolerances shown in Figure 5.1 (CJP groove welds), Figure 5.2 (PJP groove welds), or Figure 5.3 (fillet welds). Any deviation from these prequalified joint dimensions — including root opening, groove angle, root face, or land — requires WPS qualification under Clause 6.

필수 변수 — Table 5.5

Q7: A fabricator changes from E7018 to E71T-1 on a prequalified WPS. Is a new WPS required?
Answer: Yes. This is a change in 용접 공정 (SMAW to FCAW), which is an essential variable per Table 5.5. A new prequalified WPS must be written for the FCAW process. However, since both E7018 and E71T-1 are low-hydrogen electrodes (Category B in Table 5.11), the preheat 요구사항 remain unchanged.
Q8: On a prequalified WPS, the welder changes position from 1G (flat) to 3G (vertical). Does this require a new WPS?
Answer: Yes. Position is an essential variable in Table 5.5. However, because this is a prequalified WPS, no qualification testing is required — the fabricator simply writes a new prequalified WPS specifying the 3G position with appropriate parameters for vertical welding.

ASME IX 교차 질문

Q9: A welder is qualified under ASME IX for SMAW on P-Number 1 materials. Can they weld structural steel under D1.1 with no additional testing?
Answer: No. ASME IX and D1.1 maintain completely independent qualification systems. An ASME IX WPQ does not satisfy D1.1 Clause 6 Part D welder qualification requirements. The welder must qualify separately under D1.1. In practice, many welders hold both qualifications.
Q10: What is the key difference between ASME IX supplementary essential variables and D1.1 essential variables?
Answer: ASME IX has a three-tier system: essential, supplementary essential, and nonessential variables per the QW-250 series. Supplementary essential variables become essential only when impact testing is required by the construction code. D1.1 has only two tiers: essential (Table 5.5 for prequalified, Table 6.6 for qualified) and nonessential. There is no supplementary essential concept in D1.1.

"CWI Part C 시험에서 시간 관리는 매우 중요합니다. 60개의 코드북 질문에 2시간이 주어집니다. 즉, 질문당 2분입니다. 30초 이내에 표나 조항을 찾을 수 없다면, 표시하고 다음으로 넘어가십시오. Table 5.11, Table 7.7, Table 5.5, Clause 5, Clause 6에 대한 스티커 메모로 코드북을 탭하십시오 — 이들은 가장 많이 출제되는 섹션입니다."

— Field observation, CWI exam preparation practice

CWI 시험 팁: Part C 시험에서는 탭이 있고 하이라이트된 코드북을 가져올 수 있습니다(손글씨 메모는 불가). 암기보다는 빠른 표 조회에 집중하여 준비하십시오. 정답을 암기하는 것보다 정답을 어디서 찾을 수 있는지 아는 것이 더 중요합니다.

관련 표준 가이드

자주 묻는 질문

D1.1:2025 Table 5.11에 따르면, A572 Gr.50은 Group II에 속합니다. FCAW(저수소 용접 공정, Category B)의 경우, 3/4인치 초과 1-1/2인치 이하 두께에 대한 최소 예열 온도는 50°F (10°C)입니다. E71T-11을 사용하는 FCAW-S와 같은 비저수소 용접 공정을 사용하는 경우, 강재는 Category A로 이동하며, 동일한 두께 범위에 대해 150°F (65°C)가 필요합니다.

D1.1:2025 Table 7.7에 따르면, 최소 필릿 용접 크기는 예열 없이 비저수소 용접 공정을 사용할 때는 접합되는 더 두꺼운 부재(T)에 의해 결정되며, 저수소 용접 공정을 사용할 때는 접합되는 더 얇은 부재에 의해 결정됩니다. 저수소 용접 공정(E7018, E71T-1, ER70S-6)의 경우: T는 더 얇은 부재(1/2인치)와 같으며, 최소 3/16인치가 필요합니다. 예열 없는 비저수소 용접 공정의 경우: T는 더 두꺼운 부재(3/4인치)와 같으며, 최소 1/4인치가 필요합니다.

아니요. D1.1:2025는 GMAW-S(단락 이행)를 사전 인증된 용접 공정으로 포함하지 않습니다. 단락 GMAW는 특히 더 두꺼운 재료에서 불완전 융합의 위험이 높으며, Clause 6에 따라 시험을 통한 WPS 인증이 필요합니다. 다른 GMAW 이행 모드(스프레이, 글로불러, 펄스 스프레이)는 Clause 5의 다른 모든 요구 사항이 충족될 경우 사전 인증됩니다.

E7018(SMAW, A5.1)에서 E71T-1(FCAW-G, A5.20)로 변경하는 것은 용접 공정(SMAW에서 FCAW로)의 변경이며, 이는 D1.1 Table 5.5에 따른 필수 변수입니다. 이는 새로운 WPS를 요구합니다. 그러나 두 전극 모두 저수소이며 Table 5.11 Category B에 속하므로 예열 요구 사항은 동일하게 유지됩니다. 새로운 FCAW WPS는 조인트 설계가 Figures 5.1부터 5.3까지와 일치하는 것을 포함하여 다른 모든 사전 인증 조건이 충족될 경우 Clause 5에 따라 여전히 사전 인증될 수 있습니다.

D1.1 Clause 5에 따른 사전 인증된 WPS의 경우, 자세는 Table 5.5에 필수 변수로 나열되어 있습니다. 1G(평면)에서 3G(수직)로 변경하려면 새롭거나 수정된 WPS가 필요합니다. 그러나 WPS가 사전 인증되었으므로 재인증 시험이 필요하지 않습니다. 제작자는 단순히 3G 자세를 지정하는 새로운 사전 인증된 WPS를 작성하고, 수직 용접에 적합한 매개변수(일반적으로 낮은 전류, 위빙 기법)를 포함합니다. Clause 6에 따른 인증된 WPS의 경우, 용접사는 3G 자세에서 성능 인증도 받아야 합니다.